The HC3P three-phase LPHW unit heater is designed for heating large spaces such as industrial halls, warehouses and retail facilities. Equipped with a three-phase motor, it provides efficient heat distribution. The unit requires connection to a system with a heating medium, which transfers heat through the heat exchanger into the heated room. It can also operate with cold water to support air circulation and cooling.

Heating capacity 2,36 – 80,1 kW
Cooling capacity 2,6 – 30,5 kW
Airflow 2 500 – 4 000 m³/h
Ingress protection IP54

About the product

HC3P is an LPHW unit heater in a three-phase version, designed for heating large high-volume spaces — industrial halls, warehouses and commercial facilities. It requires connection to an installation with heating medium, but can also work with cold water to support air circulation and cooling in the facility.

The distinguishing feature of the unit is its single-stage, three-phase AC induction motor (400 V) with IP54 protection rating, which ensures reliable operation and high durability where constant air circulation is required. Heating capacity from 2.36 to 80.1 kW and airflow from 2,500 to 4,000 m³/h allow the unit to be matched to the needs of a large facility.

The copper-aluminium heat exchanger, available in 1-, 2- or 3-row versions, operates with a medium temperature up to 120°C and enables both heating and cooling. The expanded polypropylene (EPP) housing is lightweight, resistant to mechanical damage and provides excellent thermal and acoustic insulation, while adjustable ABS air louvres — optionally with a 360° diffuser or confusor — allow precise setting of the airflow direction.

Key features

  • Heating capacity from 2.36 kW to 80.1 kW
  • Cooling capacity from 2.6 kW to 30.5 kW
  • Airflow: from 2,500 m³/h to 4,000 m³/h
  • Three-phase AC motor 400 V (IP54)
  • EPP housing
  • Adjustable ABS air louvres (optional: 360° diffuser or confusor)
  • Made in Poland

Why choose the HC3P unit heater?

Reliable three-phase AC induction motor with IP54 protection

HC3P is the only LPHW unit heater equipped with a single-stage, three-phase AC induction motor (400 V) with IP54 protection rating.

The three-phase motor provides reliable operation and high durability in large-volume industrial facilities where constant air circulation is required. The unit is equipped with a single-stage fan.

Lightweight and durable EPP housing

The HC3P LPHW unit heater has a housing made of expanded polypropylene, a lightweight material resistant to mechanical damage that also provides excellent thermal and acoustic insulation. This housing guarantees durability in demanding industrial environments and facilitates installation thanks to its low weight.

Heat exchanger for heating and cooling

At the heart of the HC3P unit heater is a copper-aluminium heat exchanger designed for efficient heat transfer or cooling depending on the temperature of the heating medium or water. Depending on the model and design requirements, single-row, double-row or triple-row exchanger versions are available. The exchanger is designed for operation with heating medium at temperatures up to 120°C.

Cooling mode and water vapour condensation

During cooling mode operation, water vapour may condense on the unit surface. To effectively drain condensate, the use of a dedicated drip tray is recommended.

The tray is compatible with wall mounting and should be connected to the drainage system for safe removal of collected water.

Regulowane kierownice powietrza do precyzyjnej kontroli kierunku nadmuchu

Every HC3P LPHW unit heater is equipped with manually adjustable ABS air louvres for precise setting of airflow direction. Depending on requirements, a 360° diffuser or confusor can be used for even air distribution.

Dedicated HC rotating bracket

The HC rotating bracket is a practical mounting accessory dedicated to HC series LPHW unit heaters. It enables easy horizontal rotation of the unit, allowing the airflow direction to be precisely adjusted to the current needs of the users and the room layout.

The bracket also facilitates installation and servicing of the unit heater.

Do you have any questions?

Need technical support? Call us or send a message!

Models and parameters

  HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70
Product code WHHC3P20-1514 WHHC3P30-1626 WHHC3P35-1515 WHHC3P45-1627 WHHC3P50-1516 WHHC3P70-1517
Unit output [kW*] 21,4 26,4 30,3 42 44,3 60,6
Heating capacity range [kW**] 2,36 - 28,4 2,84 - 34,9 3,51 - 40,1 6,02 - 55,6 6,23 - 58,5 8,78 - 80,1
Maximum airflow [m³/h] 3200 3100 2700 2500 4000 3400
Maximum air reach [m] 19 18 15 14 21 18
Number of heat exchanger rows [pcs] 1 1 2 2 2 3
Water capacity [dm³] 0,65 0,8 1,35 1,7 1,95 2,85
Maksymalna temperatura czynnika grzewczego [°C] 120 120 120 120 120 120
Max. working pressure of heating medium [MPa] 1,6 1,6 1,6 1,6 1,6 1,6
Connection pipe diameter [in] 3/4 3/4 3/4 3/4 3/4 3/4
Voltage/Frequency [V/Hz] 400/50 400/50 400/50 400/50 400/50 400/50
Rated current [A] 0,47 0,47 0,47 0,47 0,55 0,55
Obroty silnika [obr/min.] 1380 1380 1380 1380 1350 1350
Motor power [W] 180 180 180 180 250 250
IP protection rating 54 54 54 54 54 54
Waga netto [kg] 12,5 13 14 14,5 20,5 21
Noise level [dB***] 55 55 54 54 59 58

* – przy parametrach wody 90/70°C oraz temperaturze wlotowej powietrza 0°C
** – moc maksymalna 120/90°C, 0°C na wlocie // moc minimalna 40/30°C, 20°C na wlocie
*** — measured at 5 m distance

FAQ

Yes. It simply needs to be supplied with chilled water. Cooling efficiency depends on the supply water temperature and the air inlet temperature. Due to the possibility of condensate forming, a drip tray must be used. Cooling operation is only possible when the unit heater is wall-mounted — when ceiling-mounted, the condensate would not be caught by the drip tray.

Yes, it can. Depending on requirements, a confusor (extends jet reach) or a 360° diffuser (shortens jet reach but gives better mixing with surrounding air) can additionally be fitted to the outlet.

Yes, our unit heaters are compatible with heat pumps.

No. Unit heaters can be supplied with water or glycol solution at appropriate pressure. Excessively low water pressure can negatively affect unit heater heating capacity.

Check the electrical installation connection and make sure the unit heater is connected to the supply in accordance with the wiring diagrams provided.

Book a quick

consultation

Don't waste time browsing catalogues. Leave your contact — we'll call back to ask about your facility parameters and prepare a tailored solution. What do you gain from one conversation?

  • Calculation of heating/cooling capacity requirements for your facility volume
  • Immediate confirmation of product availability and realistic delivery time
  • Selection of units that reduce electricity and heating bills, not just ones that cost less upfront
  • Direct contact with an expert who will assist with installation and design questions
Nie chcesz pisać? Zadzwoń! +48 33 500 08 88 [email protected]